Three Types of AC Power

QuantityUnitMeaning
Real powerkWAverage power converted to work, heat, light, or another useful output.
Reactive powerkVARPower exchanged with magnetic and electric fields.
Apparent powerkVACombined voltage-current burden on the electrical system.

For a sinusoidal load, these quantities form a power triangle:

kVA² = kW² + kVAR²

Power Factor Connects kW and kVA

Power factor is the ratio of real power to apparent power:

PF = kW ÷ kVA

Rearranging gives:

kW = kVA × PF     kVA = kW ÷ PF

At unity power factor, kW and kVA are numerically equal. At lower power factor, more kVA and current are required for the same kW.

Worked Example

A load uses 80 kW at 0.80 power factor:

kVA = 80 kW ÷ 0.80 = 100 kVA

The source and conductors carry 100 kVA even though only 80 kW is converted to average useful power. The corresponding reactive power is:

kVAR = √(100² - 80²) = 60 kVAR

Why Low Power Factor Matters

For fixed real power and voltage, lower power factor means higher current. Higher current increases conductor losses, voltage drop, and capacity used in transformers and generators. Some utilities apply penalties or demand charges when large customers operate below a required power factor.

Capacitor banks can reduce inductive reactive power, but correction must account for harmonics, resonance, switching, and changing load.

Why Some Equipment Is Rated in kVA

Transformers, generators, and UPS systems often have kVA limits because winding and conductor heating depend strongly on voltage and current. They may also have a separate kW limit imposed by the engine, inverter, thermal design, or energy source.

A load must fit within all applicable kW, kVA, current, transient, harmonic, and environmental limits.

Try the Calculators