When to Use This Calculator

Use this calculator when a transformer, source, or equipment impedance is given on one MVA and kV base but your study uses a different common base.

Enter Base Values

Formula Summary

Zpu,new = Zpu,old × (MVAnew ÷ MVAold) × (kVold ÷ kVnew)2

Zbase = kVLL2 ÷ MVA

Ibase = MVA × 1000 ÷ (√3 × kVLL)

Example

An impedance of 0.10 pu on a 50 MVA, 13.8 kV base becomes 0.20 pu on a 100 MVA, 13.8 kV base.

Assumptions

The MVA values are total three-phase bases and voltage is line-to-line. Base voltages on opposite sides of a transformer should follow the transformer ratio.

A base conversion changes the numerical per-unit value, not the physical impedance.

Common Mistakes

Reference Notes

These are standard per-unit base-conversion relationships for balanced three-phase power-system studies. Confirm base definitions and transformer voltage bases before combining impedances.

Related Guides