Fault MVA and Current
For a balanced three-phase fault, symmetrical RMS current and fault level are related by line-to-line voltage.
Fault MVA = √3 × kVLL × kA
Fault MVA is not energy consumed by the fault. It is a convenient way to express short-circuit strength at a bus.
Transformer Percent Impedance
Percent impedance is the percentage of rated voltage required to circulate rated current through the transformer with the opposite winding shorted. With an ideal infinite source, it limits terminal current approximately as follows:
Fault current multiplier = 100 ÷ %Z
A 5% impedance transformer therefore has an ideal terminal fault current near 20 times rated current. Upstream and downstream impedance reduce the actual value.
Why Per Unit Is Used
Per-unit analysis normalizes electrical quantities to selected MVA and voltage bases. Transformer ratios largely disappear when voltage bases follow winding ratios, making multi-voltage networks easier to combine.
Zpu,new = Zpu,old × (MVAnew ÷ MVAold) × (kVold ÷ kVnew)2
Every impedance must be on a compatible base before values are added in a network model.
Power Triangle
Real power performs net work, reactive power represents oscillating field energy, and apparent power determines the combined voltage-current burden.
MVA2 = MW2 + MVAR2
PF = MW ÷ MVA
Leading and lagging sign conventions must be confirmed because software packages and operating organizations do not all display MVAR the same way.
Study Boundaries
- Balanced three-phase equations do not represent every fault type.
- Symmetrical RMS current is different from asymmetrical or peak current.
- Transformer-only estimates omit utility, generator, motor, cable, bus, and reactor impedance.
- Equipment duty depends on the applicable calculation method and rating standard.
These simplified relationships are useful for checking and learning, but an actual protection or equipment-duty decision requires a complete system model.