Fault MVA and Current

For a balanced three-phase fault, symmetrical RMS current and fault level are related by line-to-line voltage.

Fault MVA = √3 × kVLL × kA

Fault MVA is not energy consumed by the fault. It is a convenient way to express short-circuit strength at a bus.

Transformer Percent Impedance

Percent impedance is the percentage of rated voltage required to circulate rated current through the transformer with the opposite winding shorted. With an ideal infinite source, it limits terminal current approximately as follows:

Fault current multiplier = 100 ÷ %Z

A 5% impedance transformer therefore has an ideal terminal fault current near 20 times rated current. Upstream and downstream impedance reduce the actual value.

Why Per Unit Is Used

Per-unit analysis normalizes electrical quantities to selected MVA and voltage bases. Transformer ratios largely disappear when voltage bases follow winding ratios, making multi-voltage networks easier to combine.

Zpu,new = Zpu,old × (MVAnew ÷ MVAold) × (kVold ÷ kVnew)2

Every impedance must be on a compatible base before values are added in a network model.

Power Triangle

Real power performs net work, reactive power represents oscillating field energy, and apparent power determines the combined voltage-current burden.

MVA2 = MW2 + MVAR2

PF = MW ÷ MVA

Leading and lagging sign conventions must be confirmed because software packages and operating organizations do not all display MVAR the same way.

Study Boundaries

These simplified relationships are useful for checking and learning, but an actual protection or equipment-duty decision requires a complete system model.

Power-System Calculators