Who This Guide Is For

Use this guide when you need a practical transformer sizing check from voltage, current, phase, and load type before moving into nameplate, code, and manufacturer requirements.

Formula Summary

Single-phase kVA = V × A ÷ 1000

Three-phase kVA = √3 × V × A ÷ 1000

Primary Vp, IpSecondary Vs, IskVA is conserved approximately, minus losses

Use voltage and current from the same winding side. For three-phase, use line-to-line voltage and line current.

Worked Example

A three-phase 480 V load drawing 100 A requires about 83.1 kVA.

kVA = 1.732 × 480 × 100 ÷ 1000 = 83.1 kVA

A designer would normally compare that load with the next appropriate standard transformer size after checking duty, growth, and installation conditions.

Turns and Voltage Ratio

Vp ÷ Vs = Np ÷ Ns

An ideal transformer changes current inversely so apparent power is conserved. Real transformers have losses and regulation drop.

Load Characteristics

Continuous loading, future growth, motor starting, transformer inrush, nonlinear current, harmonics, duty cycle, and load diversity can alter the required standard size.

Installation Conditions

Ambient temperature, altitude, ventilation, enclosure, sound level, insulation system, grounding, overcurrent protection, fault current, and efficiency requirements must be checked.

Calculated load kVA is not automatically the correct transformer nameplate size.

Common Mistakes

Reference Notes and Assumptions

These formulas are standard single-phase and balanced three-phase apparent-power relationships. Final sizing should follow manufacturer data, nameplate ratings, adopted electrical code requirements, and project load criteria.

Related Calculators

Related Guides